AHF Active Power Filter is a quality solution for power quality problems such as harmonics, reactive power and three-phase load imbalance. The APF in parallel with the power grid can detect the harmonics in the power grid in time, generate the reverse phase compensation current through the converter, and dynamically filter out the harmonics in the power grid.
The operation of APF is not affected by various load forms and grid structures. And does not produce harmonic oscillation (resonance) with the system, so as to achieve harmonic control under diverse loads. Active power filter can fully realize dynamic reactive power compensation, control capacitor switching, and finally improve the power factor of the power grid. At the same time, APF has the function of controlling the current imbalance of three-phase load, so as to comprehensively deal with various power quality problems .
Active Harmonic Filters (AHFs) and Passive Harmonic Filters (PHFs) are two methods used to reduce harmonic distortion in power systems. AHFs uses a real-time closed-loop control system to detect and neutralize harmonics, effectively cancels them out by injecting antiphase harmonic currents that are in phase opposite to existing harmonics, providing precise harmonic suppression, real-time correction, improved power factor, reduced equipment stress, and possible cost savings in the long term, despite higher initial costs. They are widely used in industrial facilities, data centers, commercial buildings, renewable energy facilities, and wastewater treatment plants. In contrast, PHFs consists of passive components such as resistors, capacitors, and inductors that provide a low-impedance path for harmonic currents, thereby reducing harmonic distortion. They are generally more economical, have low maintenance requirements, and are simple to install, but have limited performance, are fixed to a specific frequency, and may introduce voltage drops. Overall, AHFs is more advanced, adaptable and suitable for dynamic and complex environments, but has a higher initial cost; While PHFs is simpler and more cost-effective for harmonic suppression at fixed frequencies, it is less flexible and may not adapt to changes in system conditions.
Active power filter can improve the reliability of power grid and reduce the operating cost by reducing the harmonic level. The harmful tripping of protective devices and the harmful removal of fuses caused by harmonic thermal effect motors, transformers, switching devices and cables are greatly reduced. Equipment is also overheating less, which increases their life expectancy and reduces maintenance costs. For new installations, over-sized distribution equipment can be reconsidered to reduce harmonic sensitivity.
In manufacturing plants, variable frequency drives (VFDS) have been widely used for motor control to save energy. However, they are one of the main sources of harmonic distortion in the network. The APF active power filter can effectively eliminate harmonic distortion caused by variable speed drives in industrial applications. APF delivers power quality benefits to a variety of industries, including:
The food and beverage industry
auto industry
The oil and gas industry
Paper and chemical industries
pharmaceutical industry
Textile and clothing industry
Iron and Steel Industry
cement industry
Microelectronics manufacturer
Other industries driven by AC or DC
TYPE | Series 220V | Series 400V | Series 500V | Series 690V |
Max neutral wire current | 23A | 15A 、25A 、50A、 75A 、100A 、150A | 100A | 100A |
Nominal voltage | AC220V(-20%~+20%) | AC380V(-20%~+20%) | AC500V(-20%~+20%) | AC690V(-20%~+20%) |
Rated frequency | 50Hz±5% | |||
Network | Single phase | Three-phase three-wire/three-phase four-wire | ||
Response time | <40ms | |||
Harmonics filtering | 2th to 50th Harmonics,The number of compensation can be selected, and the range of single compensation can be adjusted | |||
Harmonic compensation rate | >92% | |||
Neutral line filtering capability | / | The filtering capacity of three-phase four-wire neutral line is 3 times of that of phase filtering | ||
machine efficiency | >97% | |||
Switching frequency | 32kHz | 16kHz | 12.8kHz | 12 .8kHz |
Feature selection | Deal with harmonics/Deal with harmonics and reactive power | Deal with harmonics/Deal with harmonics and reactive power/ Deal with harmonics and three-phase unbalance /Three options | ||
Numbers in parallel | No limitation. A single centralized monitoring module can be equipped with up to 8 power modules | |||
Communication methods | Two-channel RS485 communication interface (support GPRS/WIFI wireless communication) | |||
Altitude without derating | <2000m | |||
Temperature | -20~+50°C | |||
Humidity | <90% RH,The average monthly minimum temperature is 25℃ without condensation on the surface | |||
Pollution level | Below level Ⅲ | |||
Protection function | Overload protection, hardware over-current protection, over-voltage protection, power failure | |||
Noise | <50dB | <60dB | <65dB | |
Installation | Rack/wall hanging | Rack | ||
Into the way of line | Back entry (rack type), top entry (wall-mounted) | Top entry | ||
Protection grade | IP20 |