Voltage fluctuations can lead to unplanned production line shutdowns, causing the production line to operate abnormally and product quality to decline. It can also lead to serious consequences caused by production line disorder and disorderly start-up. In addition, the wear and tear on the machine is increased, which in turn shortens the service life and even damages the equipment. The Automatic Voltage Controller (AVC) developed by our company is an inverter-based system used to protect sensitive industrial and commercial loads from voltage fluctuations. This product can quickly and accurately compensate for voltage sags and swells, and can provide continuous voltage regulation and load voltage compensation functions. At the same time, the product has a power-off protection function, and the internal clock and user-set parameters are not affected by system power outages. The automatic voltage regulator is a three-phase five-wire single-phase compensation transformer-type voltage regulating output, which is suitable for situations where the voltage is unbalanced.
The automatic voltage regulator is composed of AC-DC-AC converter, knife switch QS, circuit breaker QF, contactor KM and compensation transformer. The AC-DC-AC converter uses fully controlled power electronics to realize bidirectional energy flow. Knife switch QS is cut to bypass state during maintenance. The contactor KM is used to turn off or on the load in the compensated state. By sampling the grid voltage, the automatic voltage regulator monitors whether the grid voltage deviates from the set value in real time. Once it deviates from the set value, it controls the AC-DC-AC converter to output a voltage with the same or opposite polarity of the grid voltage, and adjusts the voltage amplitude and polarity of the compensating transformer in series in the main loop to ensure the stability of the load terminal voltage.
Available in sizes from 30 to 500 kVA, the outdoor automatic voltage regulator provides superior voltage regulation. Capable of withstanding climactic extremes from -20° to +50°C, the AVC is uniquely suited to provide regulated precision power to mission critical outdoor loads. Each phase is independently regulated, and the PCBs are fully connectorized for ease of service. Applications include oil & gas, mining, construction, chemicals, water treatment, and defense.
Electronics and appliances: RF generator, lithography machine, etching machine, diffusion furnace, PCB drilling machine, placement machine, reflow welding;
Automobile manufacturing: spraying, drying room, welding, conveyor chain/transmission system, engine production line;
Food medical: processing and packaging production lines, blow molding machines, pharmaceutical production lines, medical imaging, freezers, compressors, ventilation systems, temperature controllers, ultra-pure water pumps, packaging equipment, high-speed filling machines;
Public facilities: elevators, escalators;
Other automation: man-machine control panel, numerical control (CNC) machine tools, robots, servo controllers, frequency converters, data centers, telecommunications, printing machines, dryers, raw material processors, extruders, PLC, contactors, regulated power supplies, sensors, AC I/O cards, timepieces, counters, safety components, relays, etc.
Type | Series 220V | Series 380V |
Norminal Voltage | AC220V (±20%) | AC380V (±20%) |
Rated Frequency | 50Hz±5% | |
Compensating Current | 30kVA | 30kVA, 45kVA, 60kVA, 80kVA, 100kVA, 120kVA, 250kVA, 500kVA |
Network | L/N | 3P4W |
Current Harmonic Distortion Rate | Increment ≤1% | |
Voltage Harmonic Distortion Rate | Increment ≤1% | |
Output Voltage | 220V±1% | |
Voltage Regulating Way | Stepless, Breakerless | |
Regulating Way | Separate phase regulation | |
Power Factor | 0.5 lag to 0.7 lead | |
Machine Efficiency | ≥95% | |
SCR Bypass | SCR Bypass Yes, with Relay | |
Display | 7-inch touch screen, providing parameter settings, power information display, fault records, historical curves, etc. | |
Protection Function | Input overvoltage/undervoltage protection, output overvoltage/undervoltage protection, input overcurrent protection, transformer overtemperature protection, output overload protection, etc. | |
Communication Methods | Four-channel RS485 communication interface (support GPRS/WIFI wireless communication), Ethernet, USB | |
Altitude without Derating | <2000m | |
Temperature | -20℃ ~ 50℃ | |
Humidity | <90% RH | |
Pollution Level | Below level Ⅲ | |
Noise | ≤65dB | |
Inlet Way | Top entry | |
Protection Grade | IP20 |